Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/05/2007 | VIOL - FIRE PROTECTION SYSTEMS | Approved | Extinguishers marked appropriatly and visable. The sprinkler coverage has been extended into the rest rooms. |
|
| 09/26/2007 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | 906.6 Unobstructed and unobscured. Portable fire extinguishers shall not be obstructed or obscured from view. In rooms or areas in which visual obstruction cannot be completely avoided, means shall be provided to indicate the locations of extinguishers. · Remove any fire extinguisher labels from locations that are no longer in use. · Replace any missing fire extinguisher labels where required. |
|
| 09/26/2007 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | 901.4 Installation. Fire protection systems shall be maintained in accordance with the original installation standards for that system. Required systems shall be extended, altered, or augmented as necessary to maintain and continue protection whenever the building is altered, remodeled or added to. Alterations to fire protection systems shall be done in accordance with applicable standards. · Extend sprinkler to provide coverage to the restrooms. · Remove the Mobil Mini or provide sprinkler protection. |