Case: T07FR01730

Parcel: 14108521C

Inspection Status: Approved

Inspection History: VIOL - MEANS OF EGRESS

Date Description Inspector Results Comments
12/03/2007 VIOL - MEANS OF EGRESS Approved Exit signs and lights installed
10/01/2007 VIOL - MEANS OF EGRESS Correction Required 1008.1.8 Door operations. Except as specifically permitted
by this section egress doors shall be readily openable from
the egress side without the use of a key or special knowledge
or effort.

Double key lock shall be removed.
09/05/2007 VIOL - MEANS OF EGRESS Correction Required 1006.1 Illumination required. The means of egress, including
the exit discharge, shall be illuminated at all times the building
space served by the means of egress is occupied.

1006.3 Illumination emergency power. The power supply for
means of egress illumination shall normally be provided by the
premise’s electrical supply.
In the event of power supply failure, an emergency electrical
system shall automatically illuminate the following areas:
1. Exit access corridors, passageways and aisles in rooms
and spaces which require two or more means of egress.
2. Exit access corridors and exit stairways located in buildings
required to have two or more exits.
3. Exterior egress components at other than the level of exit
discharge until exit discharge is accomplished for buildings
required to have two or more exits.
4. Interior exit discharge elements, as permitted in Section
1023.1, in buildings required to have two or more exits.
5. The portion of the exterior exit discharge immediately
adjacent to exit discharge doorways in buildings required
to have two or more exits.
The emergency power system shall provide power for a duration
of not less than 90 minutes and shall consist of storage
batteries, unit equipment or an on-site generator. The installation
of the emergency power system shall be in accordance with
Section 604.
- Replace missing emergency lighting.
09/05/2007 VIOL - MEANS OF EGRESS Correction Required 1011.1 Where required. Exits and exit access doors shall be
marked by an approved exit sign readily visible from any direction
of egress travel. Access to exits shall be marked by readily
visible exit signs in cases where the exit or the path of egress
travel is not immediately visible to the occupants. Exit sign
placement shall be such that no point in an exit access corridor is more than 100 feet (30 480 mm) or the listed viewing distance
for the sign, whichever is less, from the nearest visible
exit sign.
1011.2 Illumination. Exit signs shall be internally or externally
illuminated.
1011.5.3 Power source. Exit signs shall be illuminated at
all times. To ensure continued illumination for a duration of
not less than 90 minutes in case of primary power loss, the
sign illumination means shall be connected to an emergency
power system provided from storage batteries, unit equipment
or an on-site generator. The installation of the emergency
power system shall be in accordance with Section
604.
- Replace missing exit signs in accordnace with the above codes.