Inspection Status: Approved
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
| Date |
Description |
Inspector |
Results |
Comments |
| 10/09/2007 |
VIOL - BUILDING SVCS & SYSTEMS |
|
Approved |
|
| 09/04/2007 |
VIOL - BUILDING SVCS & SYSTEMS |
|
Correction Required |
IFC 605.1 Electrical cord for A/C unit, west side wall (exterior side) has enviornmental damage and is spliced in an unapproved manner. |
| 09/04/2007 |
VIOL - BUILDING SVCS & SYSTEMS |
|
Correction Required |
IFC 605.5 Extension cords shall not be substitute for permanent wiring. ( east wall, exterior side, water fountain) |
| 09/04/2007 |
VIOL - BUILDING SVCS & SYSTEMS |
|
Correction Required |
IFC 605.4 Cube type multiplug adaptors are prohibited. |
| 09/04/2007 |
VIOL - BUILDING SVCS & SYSTEMS |
|
Correction Required |
IFC 605.1 Cover plate shall be provided for open phone jack. |