Case: T07FR01718

Parcel: 12212282A


Addresses:

4300 E PIMA ST

Inspection Status: Approved

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Date Description Inspector Results Comments
05/09/2008 VIOL - BUILDING SVCS & SYSTEMS Approved
08/31/2007 VIOL - BUILDING SVCS & SYSTEMS Violation Open wire boxes/ splices:

TFC2006 / 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes.

______Cover wires in an approved manner.
08/31/2007 VIOL - BUILDING SVCS & SYSTEMS Violation Fluorescent lights touching drywall:

TFC2006/ 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated.

______ Replace or relocate lights in an approved manor. [These lights should not be touching wood. Have the lights mounted in the way approved by the "listing".]