Case: T07FR01714

Parcel: 11712098A


Addresses:

1 S CHURCH AV


Inspection Status: Violation

Inspection History: INSP - FULL

Case Number - T07FR01714

Inspection Description - INSP - FULL

Inspection Status - Violation

Date Description Inspector Results Comments
08/31/2007 INSP - FULL Violation 1). 23rd floor; Replace ceiling tiles in small or raise sprinkler heads in small closet IFC 703.1
2). 22nd floor electrical room: Fire stopping required.
Remove fire extinguisher IFC 901.6
2- exit lights are not operating. IFC 1028.4
Patch hole in wall above exit light IFC 703.1
3). Currently in all electrical and communication room, there is a need for firestopping in some degree. All we checked during re inspection. IFC 703.1.1
4). 19th floor: exit sign is not in operation. IFC 1028.4
5). 18th floor 1810, 1803, computer room, remove all extension cord not servicing permanent wiring. IFC 605.5
6). 14th floor enclosed stairwell. Please open all vents openings into enclosed stairwell to ensure fire separation requirements. IFC 703.1, 703.2
7). 11th floor: Replace ceiling tiles OR remove all combustible material from this suite. IFC 703.1
8). Suite 900: remove all boxes that may impede with exiting. IFC1028.3
9). 8TH FLOOR FBI: Mount extinguisher . IFC 901.6
Egrees illumination light shall be repaired in storage room. IFC 901.6
10). Fire stoppping on 4th floor. IFC 703.1
11).Air handler room: remove all combustible material. IFC 315.2.3
12). In the boiler room. There are extension cord being used as permanent wiring. These shall be removed. IFC 605.5
13).Clean oil leaking 3rd floor: IFC 2703.3
14). Label all containers on 3rd floor. IFC 2703.5
15). Lobby; remove all material in fire control room.
16). Fire drill is required. Date to be determined by 9-27-07