Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - FLAMMABLE LIQUIDS
Case Number - T07FR01700
Inspection Description - VIOL - FLAMMABLE LIQUIDS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/25/2007 | VIOL - FLAMMABLE LIQUIDS | Approved | Pipe joints have been repaired. The emergency vents are installed. | |
09/05/2007 | VIOL - FLAMMABLE LIQUIDS | Correction Required | 3403.6.10 Pipe joints. Joints shall be liquid tight and shall be welded, flanged or threaded except that listed flexible connectors are allowed in accordance with Section 3403.6.9. Threaded or flanged joints shall fit tightly by using approved methods and materials for the type of joint. - All connections to the tank shall meet this requirement. Remove the rubber hose and rags stuffed into the tank outlet. |
|
09/05/2007 | VIOL - FLAMMABLE LIQUIDS | Correction Required | 3404.2.7.4 Emergency venting. Stationary, above-ground tanks shall be equipped with additional venting that will relieve excessive internal pressure caused by exposure to fires. - Emergency venting shall be installed on both tanks. |
|
09/05/2007 | VIOL - FLAMMABLE LIQUIDS | Correction Required | 3404.2.7.3.3 Vent pipe outlets. Vent outlets on atmospheric tanks storing Class IIIB liquids are allowed to discharge inside a building if the vent is a normally closed vent. - The pumps currently on the tanks with the integrated vent meet this requirement. |