Case: T07FR01700

Parcel: 13613001M

Inspection Status: Approved

Inspection History: VIOL - FLAMMABLE LIQUIDS

Case Number - T07FR01700

Inspection Description - VIOL - FLAMMABLE LIQUIDS

Inspection Status - Approved

Date Description Inspector Results Comments
10/25/2007 VIOL - FLAMMABLE LIQUIDS Approved Pipe joints have been repaired. The emergency vents are installed.
09/05/2007 VIOL - FLAMMABLE LIQUIDS Correction Required 3403.6.10 Pipe joints. Joints shall be liquid tight and shall be welded, flanged or threaded except that listed flexible connectors are allowed in accordance with Section 3403.6.9. Threaded or flanged joints shall fit tightly by using approved methods and materials for the type of joint.
- All connections to the tank shall meet this requirement. Remove the rubber hose and rags stuffed into the tank outlet.
09/05/2007 VIOL - FLAMMABLE LIQUIDS Correction Required 3404.2.7.4 Emergency venting. Stationary, above-ground tanks shall be equipped with additional venting that will relieve excessive internal pressure caused by exposure to fires.
- Emergency venting shall be installed on both tanks.
09/05/2007 VIOL - FLAMMABLE LIQUIDS Correction Required 3404.2.7.3.3 Vent pipe outlets. Vent outlets on atmospheric tanks storing Class IIIB liquids are allowed to discharge inside a building if the vent is a normally closed vent.
- The pumps currently on the tanks with the integrated vent meet this requirement.