| 08/27/2007 |
COMPL - INITIAL INSPECTION |
|
Approved |
Sprinkler system out of service due to sprinkler head activation. |
| 08/27/2007 |
COMPL - INITIAL INSPECTION |
|
Approved |
Building sprinkler head activated due to kitchen hood system for solid fuel cooking equipment being overwhelmed. System was overwhelmed because it needed to be cleaned and had a reduced air flow. Gave owner a notice of violation ordering that the cooking equipment not be used until hood was cleaned and moving air at the required rate. |