Case: T07FR01631

Parcel: 118061640


Addresses:

1952 W MISTLETOE CI

Inspection Status: Approved

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Date Description Inspector Results Comments
09/14/2007 VIOL - BUILDING SVCS & SYSTEMS Approved
08/22/2007 VIOL - BUILDING SVCS & SYSTEMS Correction Required IFC 605.1 Abate electrical hazards:
1.) Bdrm. #3, closet, exposed wiring.
2.) improper splicing on furnace.
3.) Wiring into main (exterior) electrical panel. Permanent wring below 7 ft. is requirered to be protected
(conduit) as per code.
4.) Wiring for light switch opposit main panel requires
approved protection into electrical box.
5.) Carport storage room, exposed wiring on light fixture,
secure fixture in accordance to code.
08/22/2007 VIOL - BUILDING SVCS & SYSTEMS Correction Required IFC 605.6 Extensiopn cords shall not be a substitute for permanent wiring.
1.) furnace room
2.) carport storage room