Case: T07FR01603

Parcel: 13314462B


Addresses:

6555 E SPEEDWAY BL


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T07FR01603

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
09/27/2007 INSP - FULL Approved approved
08/17/2007 INSP - FULL Violation 1). Sprinkler test and inspection report shall be submitted, with all required repairs completed. IFC 901.6
2). Fire alarm test report shall be submitted. IFC 901.6
3). Repair hole near front desk. IFC 703.1
4). Mount portable fire extinguishers (2) in galley area. IFC 906.7
5). Repair additional power cord in galley area. IFC 605
6). Liquor room: Replace ceiling tiles IFC 703.1
7). Repair wall in galley area. IFC 703.1
8). Kitchen: Class K portable fire extinguishers shall be serviced. IFC 901.6
9). Kitchen: Hood extinguishing system shall be serviced every 6 months as per IFC 904.5.1 which states:
904.5.1 System test. Systems shall be inspected and tested for proper operation at 6-month intervals. Tests shall include a check of the detection system, alarms and releasing devices, including manual stations and other associated equipment. Extinguishing system units shall be weighed and the required amount of agent verified. Stored pressure- type units shall be checked for the required pressure. The cartridge of cartridge-operated units shall be weighed and replaced at intervals indicated by the manufacturer.
10). Extinguisher shall have the 1-year servicing in laundry room and engineering office. IFC 901.6.