Case: T07FR01572

Parcel: 12708187F


Addresses:

5405 E BROADWAY BL


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T07FR01572

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
08/29/2007 INSP - FULL Approved Final inspection
08/14/2007 INSP - FULL Violation 2006 IFc-903 The fifre sprinkler controls and connections outside is covered with brush this needs to be cut down.
2006 IFC-315.2 .1 In the restroom sprinkler head is coverd by storage, need to remove storage.18 inches shall be below the sprinkler head.
2006 IFC-703.1 Tile missing back area dog bed. Fire resistive construction shall be kept to prevent fire spread.
2006 IFC-605.5 Extension cord in the back area employees room only. Replace with power surge protector.