Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - MEANS OF EGRESS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/08/2007 | VIOL - MEANS OF EGRESS | Approved | Replaced lock with panic hardware and removed electric locking device. Also added door to their alarm system. | |
| 08/13/2007 | VIOL - MEANS OF EGRESS | Violation | Misleading Exit signs: TFC2006/ 1028.4 Exit signs. Exit signs shall be installed and maintained in accordance with section 1011. Decorations, furnishings,equipment, or adjacent signage that impairs the visibility of exit signs, creates confusion or prevents identification of the exit shall not be allowed. _____ Change direction of exit sign to point to an exit, and place an exit sign over that door as well. OR.... The sign may remain in the current position, and no sign is required, but you must place a Thumb turn lock on the front door (see below- key lock violation)]. Either way is acceptable. |
|
| 08/13/2007 | VIOL - MEANS OF EGRESS | Violation | Double keyed lock on door: TFC2006/ 1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. ______ Remove keyed dead bolt. |