Case: T07FR01551

Parcel: 133170600


Addresses:

410 N WILMOT RD


Inspection Status: Approved

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T07FR01551

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Approved

Date Description Inspector Results Comments
05/09/2008 VIOL - BUILDING SVCS & SYSTEMS Approved
12/14/2007 VIOL - BUILDING SVCS & SYSTEMS Partial Approval Extension cord by TV [kit]
08/10/2007 VIOL - BUILDING SVCS & SYSTEMS Violation Extension cords:

TFC2006/ 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances.

_____Replace with approved power strip.
08/10/2007 VIOL - BUILDING SVCS & SYSTEMS Violation Wires bad on side-by-side unit:

TFC2006/ 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated.

______ Replace wires in an approved manor. [and check all other equipment for electrical hazards]
08/10/2007 VIOL - BUILDING SVCS & SYSTEMS Violation Multiplug adapters:

TFC2006/ 605.4 Multiplug adapters. Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited.

______Remove noncomplying devices.