Case: T07FR01543

Parcel: 12701008A


Addresses:

5205 E BROADWAY BL


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T07FR01543

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
08/23/2007 INSP - FULL Approved Final inspection
08/09/2007 INSP - FULL Violation 2006 IFC-1006.1 The east exit shall be illuminated. Exit discharge shall be illuminated.
2006 IFC-901.6 Fire extinguishers shall be serviced annually and shall have a current service tag attached.
2006 IFC-1011.5.3 The illuminated exit light in back of the kitchen area needs bulbs replacement.
2006 IFC-315.2.1 Sprinkler in the freezer, storage shall be 18 inches below and to the side of the sprinkler heads.
2006 IFC-510.1 Sprinkler system shall have the label RISER ROOM on the door so firefighters can locate quicker.
2006 IFC-506.1 The keys for the business shall be in the supra box, this is to prevent damaging the doors to access the building.