Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/04/2007 | INSP - FULL | Approved | ||
| 08/07/2007 | INSP - FULL | Violation | On 7-26-07 , a fire prevention inspection was conducted at PAB 1400 South Alvernon Way, in Tucson, Arizona. The following Tucson Fire Code Violation(s) was noted: 1). Currently there is combustible storage in the attic. This is in violation of IFC 314.2.4 which states: 315.2.4 Attic, under-floor and concealed spaces. Attic, under-floor and concealed spaces used for storage of combustible materials shall be protected on the storage side as required for 1-hour fire-resistance-rated construction. Openings shall be protected by assemblies that are self-closing and are of noncombustible construction or solid wood core not less than 1.75 inches (44.5 mm) in thickness. Storage shall not be placed on exposed joists. Exceptions: 1. Areas protected by approved automatic sprinkler systems. 2. Group R-3 and Group U occupancies. 2). Currently there is an opening, or door in to ceiling that must be repaired by rated material. IFC 703.1 3). Clearance of 30 inches must be made of all electrical service and panels. IFC 605.3 |