Case: T07FR01498

Parcel: 130070070


Addresses:

1330 S ALVERNON WY

Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
10/26/2007 INSP - FULL Approved
08/07/2007 INSP - FULL Violation 1). Electrical face plated shall be re installed in the following areas:, Supply room, (2) in rack and frame room, and in body area. IFC 605.1
2). All extinguishers shall be Size 40-B and shall be no less than 30 feet from flammable liquid operations. All others shall be removed. IFC 906.3.2
3). Repair drywall in frame and rack shop. IFC 703.1
4). Fire sprinkler test and inspection report shall be submitted and all repairs shall be completed. IFC 901.6
5). Remove weeds from sprinkler and fire dept connections. IFC 901.6