Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - MEANS OF EGRESS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/11/2007 | VIOL - MEANS OF EGRESS | Approved | All o.k. 9/6. | |
| 08/07/2007 | VIOL - MEANS OF EGRESS | Correction Required | -Exit signs out of service in emergency mode. (Computer room) (Chapter room) 2006 IFC-1011.5.3 ***Repair exit signs to illuminate during power interruptions. |
|
| 08/07/2007 | VIOL - MEANS OF EGRESS | Correction Required | -Exit door difficult to open, should open freely. (Chapter room) 2006 IFC 1008.1.9 ***Repair door to open freely, with less than 15lbs. unlatching force. |
|
| 08/07/2007 | VIOL - MEANS OF EGRESS | Correction Required | -Emergency lighting out of service. (Chapter room) 2006 IFC-1027.5 ***Repair emergency lighting. |