Inspection Status: Violation
Inspection History: INSP - FULL
Case Number - T07FR01472
Inspection Description - INSP - FULL
Inspection Status - Violation
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/03/2007 | INSP - FULL | Violation | 2006 IFC-10011.5.3 Exit illumination lights shall be in good working order at all times.Check the batteries and light bulbs if need to replace. 2006 IFC-904.11.5.2 Fire extinguishers shall be serviced. 2006 IFC-904.11.6.4 Hood system sprinkler sprinklers shall be serviced every 6 months and shall have a current service tag attached. 2006IFC-3404.3.4 Gas can under the desk shall remove from restaurant, class A flammable not allowed in in group A occupancy. 2006 IFC-605 Bulb in freezer shall have the protected cover to prevent shock. 2006 IFC-605.5 Extension cord under mat shall not be a substitute for permanent wiring. 2006 IFC-110 Need the Certificate of Occupancy posted or filed in the business. |