Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
Case Number - T07FR01342
Inspection Description - VIOL - FIRE PROTECTION SYSTEMS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/02/2007 | VIOL - FIRE PROTECTION SYSTEMS | Approved | ||
07/20/2007 | VIOL - FIRE PROTECTION SYSTEMS | Compliance | Conducted a follow-up inspection to confirm status of fire alarm and fire sprinkler sysems. Both systems continued in proper standby mode with no false alarms during the 24hr period. Systems called back in service and FIRE DISPATCH notified of fully operational systems. CLOSED | |
07/18/2007 | VIOL - FIRE PROTECTION SYSTEMS | Approved | 901.6 Inspection, testing and maintenance. Fire detection, alarm and extinguishing systems shall be maintained in an operative condition at all times, and shall be replaced or repaired where defective. THREE FAULSE ALARMS WITH IN 24 HR PERIORD. EN18 CONTACT MA29 AND A PROPERTEY REP. 1. HAVE ALL FIRE PROCTION SYS.SERVICED AND HAVE PAPER DOC. ON SIT AND HAVE COPY FOR INSPECTOR. 2. PLACE CONTACT NUMBERS IN KNOT BOX FOR SUPPRESSION UNITS. |