Inspection History Details
Inspection Status: Violation
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
Case Number - T07FR01327
Inspection Description - VIOL - FIRE PROTECTION SYSTEMS
Inspection Status - Violation
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/16/2007 | VIOL - FIRE PROTECTION SYSTEMS | Violation | POWER FAILURE APPROX. 12:30 AM, AND RESTORED 30 MIN. LATER. EN12 DISPATCHED 5:30 AM, UNABLE TO RESET PANEL IFC 2003 901.6.2 FIRE ALARM SYS. MUST BE MAINTAINED. 1. HAVE ALARM REPAIRED WITH IN 8HR 2. NEED A FIRE WATCH. ALARM IS PART OF SPRINKLER SYS. 3. BATTERY SHOWS SIGNS OF FAILURE. 4. FAX REPAIR REPORT TO FP. OFFICE 5. DUE TO HX. OF PROBLEMS PANEL MAY NEEDED TO BE REPLACED |
|
07/16/2007 | VIOL - FIRE PROTECTION SYSTEMS | Approved | STORE MANAGER HAVE PANEL REPAIRED WITHIN 4 HR AND FAX REPART TO FP. SYS. BACK INSERVICE. |