Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T07FR01327

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Violation

Date Description Inspector Results Comments
07/16/2007 VIOL - FIRE PROTECTION SYSTEMS Violation POWER FAILURE APPROX. 12:30 AM, AND RESTORED 30 MIN. LATER. EN12 DISPATCHED 5:30 AM, UNABLE TO RESET PANEL
IFC 2003 901.6.2 FIRE ALARM SYS. MUST BE MAINTAINED.
1. HAVE ALARM REPAIRED WITH IN 8HR
2. NEED A FIRE WATCH. ALARM IS PART OF SPRINKLER SYS.
3. BATTERY SHOWS SIGNS OF FAILURE.
4. FAX REPAIR REPORT TO FP. OFFICE
5. DUE TO HX. OF PROBLEMS PANEL MAY NEEDED TO BE REPLACED
07/16/2007 VIOL - FIRE PROTECTION SYSTEMS Approved STORE MANAGER HAVE PANEL REPAIRED WITHIN 4 HR AND FAX REPART TO FP. SYS. BACK INSERVICE.