Case: T07FR01313

Parcel: 110072350


Addresses:

4165 E GRANT RD

Inspection Status: Approved

Inspection History: VIOL - PRECAUTION AGAINST FIRE

Date Description Inspector Results Comments
07/16/2007 VIOL - PRECAUTION AGAINST FIRE Approved
07/12/2007 VIOL - PRECAUTION AGAINST FIRE Violation Tires storage by fence:
315.3 Outside storage. Outside storage of combustible materials shall not be located within 10 feet (3048 mm) of a property line.
Exceptions:
1. The separation distance is allowed to be reduced to 3 feet (914 mm) for storage not exceeding 6 feet (1829 mm) in height.
2. The separation distance is allowed to be reduced when the fire code official determines that no hazard to the adjoining property exists.

______ Allow at least 3' of clearance for fire lines between tires and fence, at the locations with exposures.

Re-inspection date scheduled on or after July 26, 2007.
If you have any questions or concerns please call Inspector Cobb at 791-4502
Thank you,

_____________________________________________
Brian Cobb, Inspector, Tucson Fire Department


___________________I have received a copy of this inspection report.
Building Representative


_____________________________________________
Captain