Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
Case Number - T07FR01311
Inspection Description - VIOL - FIRE PROTECTION SYSTEMS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/01/2007 | VIOL - FIRE PROTECTION SYSTEMS | Approved | ||
07/11/2007 | VIOL - FIRE PROTECTION SYSTEMS | Violation | Class K Extinguisher: 904.11.5 Commercial cooking equipment. Portable fire extinguishers shall be provided within a 30-foot (9144 mm) travel distance of commercial-type cooking equipment. Cooking equipment involving vegetable or animal oils and fats shall be protected by a Class K rated portable extinguisher. ______A K class extinguisher shall be installed according to this code. Note: greater than 10' and less than 30', near "way out", not in a corner or area of more ganger. Call me if you have any questions. Re-inspection date scheduled on or after July 26, 2007. If you have any questions or concerns please call Inspector Cobb at 791-4502 Thank you, _____________________________________________ Brian Cobb, Inspector, Tucson Fire Department ___________________I have received a copy of this inspection report. Building Representative _____________________________________________ Captain |