Case: T07FR01303

Parcel: 136061570


Addresses:

2430 S HARRISON RD


Inspection Status: Approved

Inspection History: VIOL - FLAMMABLE LIQUIDS

Case Number - T07FR01303

Inspection Description - VIOL - FLAMMABLE LIQUIDS

Inspection Status - Approved

Date Description Inspector Results Comments
12/26/2007 VIOL - FLAMMABLE LIQUIDS Approved Vents installed. Permits will be issued to safetykleen
07/19/2007 VIOL - FLAMMABLE LIQUIDS Correction Required 3404.2.7.3.3 Vent pipe outlets. Vent pipe outlets for tanks storing Class I, II or IIIA liquids shall be located such that the vapors are released at a safe point outside of buildings and not less than 12 feet (3658 mm) above the adjacent ground level. Vapors shall be discharged upward or horizontally away from adjacent walls to assist in vapor dispersion. Vent outlets shall be located such that flammable vapors will not be trapped by eaves or other obstructions and shall be at least 5 feet (1524 mm) from building openings or lot lines of properties that can be built upon. Vent outlets on atmospheric tanks storing Class IIIB liquids are allowed to discharge inside a building if the vent is a normally closed vent.
07/19/2007 VIOL - FLAMMABLE LIQUIDS Correction Required 3404.2.7.4 Emergency venting. Stationary, above-ground tanks shall be equipped with additional venting that will relieve excessive internal pressure caused by exposure to fires. Emergency vents for Class I, II and IIIA liquids shall not discharge inside buildings. The venting shall be installed and maintained in accordance with Section 2.2.5.2 of NFPA 30.
07/19/2007 VIOL - FLAMMABLE LIQUIDS Continued Deliverd the report of violations. RI in two weeks