Inspection Status: Approved
Inspection History: VIOL - MEANS OF EGRESS
| Date |
Description |
Inspector |
Results |
Comments |
| 08/21/2007 |
VIOL - MEANS OF EGRESS |
|
Approved |
all corrections have been made. |
| 07/19/2007 |
VIOL - MEANS OF EGRESS |
|
Violation |
IFC 1008.1.2 Doors shall swing in the direction of egress in an H class occupancy. Cause your doors to swing in the direction of egress or reduce your amounts of liquid oxygen to below the max allowable limits. |