Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
Case Number - T07FR01278
Inspection Description - VIOL - FIRE PROTECTION SYSTEMS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/21/2007 | VIOL - FIRE PROTECTION SYSTEMS | Approved | all corrections have been made. | |
07/19/2007 | VIOL - FIRE PROTECTION SYSTEMS | Violation | IFC 906.1 Portable fire extinguishers shall be installed in a group B and group H occupancies. Place a minimum of a 2-A extinguisher in the B; a minimum rated 4- A in the storage are with H classification. Extinguishers will be mounted in a highly visible area and near to your exits. Install in accordance with NFPA 10. |