Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Case: T07FR01278

Parcel: 132150240


Addresses:

3690 S PARK AV #807

Inspection Status: Approved

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Date Description Inspector Results Comments
08/21/2007 VIOL - FIRE PROTECTION SYSTEMS Approved all corrections have been made.
07/19/2007 VIOL - FIRE PROTECTION SYSTEMS Violation IFC 906.1 Portable fire extinguishers shall be installed in a group B and group H occupancies. Place a minimum of a 2-A extinguisher in the B; a minimum rated 4- A in the storage are with H classification. Extinguishers will be mounted in a highly visible area and near to your exits. Install in accordance with NFPA 10.