Inspection History Details
Inspection Status: Correction Required
Inspection History: VIOL - MEANS OF EGRESS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/05/2007 | VIOL - MEANS OF EGRESS | Correction Required | TFC 1008.1.8.3 The exit doors near the ice machine shall have this wording posted. | |
| 07/05/2007 | VIOL - MEANS OF EGRESS | Correction Required | TFC 1008.1.8 #1.All exit doors with a double keyed locking device shall have thumb turn locks installed. Exceptions: Doors with panic hardware and the main exit with approved wording. #2.Remove the double keyed lock from the trucker lounge exit fence, replace it with a thumb turn lock. #3.Remove the extra panic hardware device from the exit door near the tobacco. |
|
| 07/05/2007 | VIOL - MEANS OF EGRESS | Correction Required | TFC 1027.2 The exit door located in the auto shop shall not be obstructed. | |
| 07/05/2007 | VIOL - MEANS OF EGRESS | Correction Required | TFC 1027.6 Remove the door handle from the exit door in thye auto shop. | |
| 07/05/2007 | VIOL - MEANS OF EGRESS | Correction Required | TFC 1026.5 The exit sign located by the pharmacy shall have emergency back-up power. | |
| 07/05/2007 | VIOL - MEANS OF EGRESS | Correction Required | TFC 1011.1 Remove the cover arrow from the exit sign that is over the entrance to the auto shop.{ Remove the right arrow.} |