Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case: T07FR01251

Parcel: 133170630


Addresses:

350 N WILMOT RD


Inspection Status: Closed

Inspection History: INSP - AST/UST

Case Number - T07FR01251

Inspection Description - INSP - AST/UST

Inspection Status - Closed

Date Description Inspector Results Comments
08/14/2007 INSP - AST/UST Closed Site inspection, AST has been removed and UST is back in service.
08/01/2007 INSP - AST/UST Continued Tank has been relined and fuel placed back in it. The portable tank is planned to be moved this week and has been cleaned out. Awaiting documentation of the re-lining process.
07/09/2007 INSP - AST/UST Continued MA27 and MA28 conducted a meeting with Kevin Nelson, Dave Koepp of Carondelet and Rod Rayes of Southwest Fuel Care @ St Joseph's Hospital. We informed them of our permit process and distributed copies to all parties. Tank on site is non-permitted, non-compliant and shall be replaced ASAP. Tank has been labeled, vehicle impact protected and hatch used as temporary emergency vent. It will be grounded to existing UST and shall not be fueled.
07/03/2007 INSP - AST/UST Continued Permit was issued for defueling a UST and they have installed an AST for temporary use until the the UST is relined. No listing on AST, contractor to send us specs on the AST.