Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/18/2007 | INSP - FULL | Approved | approved | |
| 07/02/2007 | INSP - FULL | Violation | On 6-25-07, a fire prevention inspection was conducted at front yard of 4033 East 32nd trough as complaint, which was filed with the fire department. The following Tucson Fire Code Violation(s) was noted: 1). Currently there are over 30 gallons of flammable liquids, this is in excess over the allowable amount. The fire code states: 3404.3.4.4 Liquids for maintenance and operation of equipment. In all occupancies, quantities of flammable and combustible liquids in excess of 10 gallons (38 L) used for maintenance purposes and the operation of equipment shall be stored in liquid storage cabinets in accordance with Section 3404.3.2. Quantities not exceeding 10 gallons (38 L) are allowed to be stored outside of a cabinet when in approved containers located in private garages or other approved locations. Please reduce the gallons to 10 gallons only. Vapors count towards gallons. In addition, it is noticed that smoking materials have been discarded around the storage of the flammable materials. Please do not discard or use smoking materials around flammable liquids. |