Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - FIRE PROTECTION SYSTEMS
Case Number - T07FR01230
Inspection Description - VIOL - FIRE PROTECTION SYSTEMS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/08/2007 | VIOL - FIRE PROTECTION SYSTEMS | Approved | Follow up on 7/10, All O.K. | |
06/29/2007 | VIOL - FIRE PROTECTION SYSTEMS | Correction Required | Went to Chili's, spoke with Manager Nick Sickler. In the rear of building, FDC's had a garden hose wrapped around them. Also, box storage blocking acces to FDC's. The FDC's are protected by a chain link fence, along with dumpsters, grease collection and utilities. A knox padlock will not work with the gate. The management would be content to have current lock broken, if neccessary. The garden hose and storage will be moved today, 6/29, and BCORRAL1 will follow up in one week. 912.3 Access. Immediate access to fire department connections shall be maintained at all times and without obstruction by fences, bushes, trees, walls or any other object for a minimum of 3 feet (914 mm). |