Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - MOTOR FUEL DISPENSING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/26/2007 | VIOL - MOTOR FUEL DISPENSING | Approved | ||
| 08/27/2007 | VIOL - MOTOR FUEL DISPENSING | Continued | view obstructions removed. all dispensers are visable | |
| 06/27/2007 | VIOL - MOTOR FUEL DISPENSING | Correction Required | 2205.2.2 Emergency shutoff valves. Automatic-closing emergency shutoff valves required by Section 2206.7.4 shall be checked not less than once per year by manually tripping the hold-open linkage. - Provide documentation of this test. |
|
| 06/26/2007 | VIOL - MOTOR FUEL DISPENSING | Correction Required | 2204.2.4 Obstructions to view. Dispensing devices shall be in clear view of the attendant at all times. Obstructions shall not be placed between the dispensing area and the attendant. - Remove all items blocking the clear view of the dispensers. Coke machine, posters and stock for sale. Also adjust mirrors to provide a clear view of the dispensers. Dispenser 7/8 is not visable. |
|
| 06/26/2007 | VIOL - MOTOR FUEL DISPENSING | Correction Required | 2203.2 Emergency disconnect switches. An approved, clearly identified and readily accessible emergency disconnect switch shall be provided at an approved location, to stop the transfer of fuel to the fuel dispensers in the event of a fuel spill or other emergency. An emergency disconnect switch for exterior fuel dispensers shall be located within 100 feet of, but not less than 20 feet from, the fuel dispensers. - The Emergency disconnect switches shall be relocated or dispenser 7/8 moved. permits are required. |