Case: T07FR01199

Parcel: 116126290

Inspection Status: Approved

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Date Description Inspector Results Comments
09/26/2007 VIOL - BUILDING SVCS & SYSTEMS Approved
08/27/2007 VIOL - BUILDING SVCS & SYSTEMS Continued The circuit panels are clear of obstructions and the junction box has been repaired.
06/26/2007 VIOL - BUILDING SVCS & SYSTEMS Correction Required 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. Electrical wiring, devices, appliances and other equipment that is modified or damaged and constitutes an electrical shock or fire hazard shall not be used.
- The cord to cathotic protection shall be repaired in accordance with the electrical code.
06/26/2007 VIOL - BUILDING SVCS & SYSTEMS Correction Required 605.3Working space and clearance. A working space of not less than 30 inches (762 mm) in width, 36 inches (914 mm) in depth and 78 inches (1981 mm) in height shall be provided in front of electrical service equipment. Where the electrical service equipment is wider than 30 inches (762 mm), the working space shall not be less than the width of the equipment. No storage of any materials shall be located within the designated working space.
- Clearance around the circuit breaker panels and power shutoff devices shall be maintained. (Storage/ restrooms)
06/26/2007 VIOL - BUILDING SVCS & SYSTEMS Correction Required 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes.
- Repair or replace the open junction box near the air/ water service. (Under the Conoco sign)