Case: T07FR01198

Parcel: 116126290

Inspection Status: Correction Required

Inspection History: VIOL - MOTOR FUEL DISPENSING

Date Description Inspector Results Comments
08/08/2007 VIOL - MOTOR FUEL DISPENSING Correction Required
07/03/2007 VIOL - MOTOR FUEL DISPENSING Approved
06/26/2007 VIOL - MOTOR FUEL DISPENSING Correction Required 2203.1 Location of dispensing devices. Dispensing devices
shall be located as follows:
2. Ten feet (3048 mm) or more from buildings having combustible
exterior wall surfaces or buildings having
noncombustible exteriorwall surfaces that are not part of
a 1-hour fire-resistance-rated assembly or buildings having
combustible overhangs.
4. Such that the nozzle, when the hose is fully extended,
will not reach within 5 feet (1524 mm) of building openings.
- #5/6 dispenser hose will reach the only exit of the kiosk-
06/26/2007 VIOL - MOTOR FUEL DISPENSING Correction Required 2203.2 Emergency disconnect switches. An approved,
clearly identified and readily accessible emergency disconnect
switch shall be provided at an approved location, to stop the
transfer of fuel to the fuel dispensers in the event of a fuel spill
or other emergency. An emergency disconnect switch for exterior fuel dispensers shall be located within 100 feet (30 480
mm) of, but not less than 20 feet (6096 mm) from, the fuel dispensers.
- #7/8 dispenser is too close to the E-stop