Inspection History Details
Inspection Status: Correction Required
Inspection History: VIOL - MOTOR FUEL DISPENSING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/08/2007 | VIOL - MOTOR FUEL DISPENSING | Correction Required | ||
| 07/03/2007 | VIOL - MOTOR FUEL DISPENSING | Approved | ||
| 06/26/2007 | VIOL - MOTOR FUEL DISPENSING | Correction Required | 2203.1 Location of dispensing devices. Dispensing devices shall be located as follows: 2. Ten feet (3048 mm) or more from buildings having combustible exterior wall surfaces or buildings having noncombustible exteriorwall surfaces that are not part of a 1-hour fire-resistance-rated assembly or buildings having combustible overhangs. 4. Such that the nozzle, when the hose is fully extended, will not reach within 5 feet (1524 mm) of building openings. - #5/6 dispenser hose will reach the only exit of the kiosk- |
|
| 06/26/2007 | VIOL - MOTOR FUEL DISPENSING | Correction Required | 2203.2 Emergency disconnect switches. An approved, clearly identified and readily accessible emergency disconnect switch shall be provided at an approved location, to stop the transfer of fuel to the fuel dispensers in the event of a fuel spill or other emergency. An emergency disconnect switch for exterior fuel dispensers shall be located within 100 feet (30 480 mm) of, but not less than 20 feet (6096 mm) from, the fuel dispensers. - #7/8 dispenser is too close to the E-stop |