Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T07FR01196
Inspection Description - INSP - FULL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/23/2007 | INSP - FULL | Approved | Re inspections were conducted: Aug. 13, 1007 August 22, 2007 August 23, 2007 |
|
08/23/2007 | INSP - FULL | Approved | All Items Abates August 23, 2007 | |
06/26/2007 | INSP - FULL | Correction Required | FIRE INSPECTION REPORT 6/25/2007 Big Lots ATTN: Susan Treadway 2520 S. Harrison Tucson, AZ. 85747 Mrs. Treadway The Tucson Fire Department has conducted a fire safety inspection at the above stated business on June 25, 2007. Below is a list of violations that shall be corrected to provide compliance with the applicable codes, regulations and ordinances. Compliance is required by the 2003 International Fire Code (with modifications). A Re-inspection will be performed on or about July 9, 2007 Notice of Violations: 1026.3 Exit sign illumination. Exit signs shall be internally or externally illuminated. The face of an exit sign illuminated from an external source, shall have an intensity of not less than foot-candles (54 lux). Internally illuminated signs shall provide equivalent luminance and be listed for the purpose. · Front Entrance · Outside the Manager's office · Doors numbered: 1,2,3,4 _____ 703.1 Maintenance. The required fire-resistance rating of fire-resistance-rated construction (including walls, fire stops, shaft enclosures, partitions and floors) shall be maintained. Such elements shall be properly repaired, restored or replaced when damaged, altered, breached or penetrated: · Replace the missing/ misplaced ceiling tiles in the entry area _____ 3003.3 Security. Compressed gas containers, cylinders, tanks and systems shall be secured against accidental dislodgment and against access by unauthorized personnel in accordance with Sections 3003.3.1 through 3003.3.3. · Secure the compressed gas cylinder in the cash office. _____ 605.5 Extension Cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact… · In the break room behind the soda machines 1008.1.9 Panic and fire exit hardware. Where panic and fire exit hardware is installed, it shall comply with the following: 1. The actuating portion of the releasing device shall extend at least one-half of the door leaf width. 2. A maximum unlatching force of 15 pounds (67 N). Each door in a means of egress from an occupancy of Group A or E having an occupant load of 100 or more and any occupancy of Group H-1, H-2, H-3 or H-5 shall not be provided with a latch or lock unless it is panic hardware or fire exit hardware. · Panic hardware on the door next to the riser shall operate when less than 15lbs of force is applied to the latch side. _____ 901.4.1 Required fire protection systems. Fire protection systems required by this code or the International Building Code shall be installed, repaired, operated, tested and maintained in accordance with this code. · Provide current result of the sprinkler test · Remove the ceiling insulation that is blocking the operation of the sprinkler head: hear the upstairs bathrooms. _____ 315.2.1 Ceiling clearance. Storage shall be maintained 2 feet (610 mm) or more below the ceiling in nonsprinklered areas of buildings... · In the "Defective Room." · Maintenance closet 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated. Identified hazardous electrical conditions in permanent wiring shall be brought to the attention of the code official responsible for enforcement of the ICC Electrical Code. Electrical wiring, devices, appliances and other equipment that is modified or damaged and constitutes an electrical shock or fire hazard shall not be used: · Abate electrical hazard in the areas near the old catwalk. · Replace missing cover-plate outside the maintenance room in hallway · Repair j-box/light switch in the "Fixture Room." · Replace missing cover-plate in the "Carpet Room." 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply · All emergency back-up lighting shall operate throughout the business. The Tucson Fire Department is committed to the protection of your property. Your help as a business owner and as a citizen is greatly appreciated. __________________________________________________ Property owner or Property Representative Signature _________________________________ Abatement Date __________________________ Captain Signature Sincerely, Jimmy R. Davis, Jr Fire Inspector Tucson Fire Department |