Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T07FR01187
Inspection Description - INSP - FULL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
07/06/2007 | INSP - FULL | Approved | Final inspection all violations complete. | |
06/22/2007 | INSP - FULL | Correction Required | 2003 IFC- 703 Ceiling tile missing in the kitchen area.Need to maintain the fire resistive construction. 2003 IFC-508 The riser room shall be labeled. RISER ROOM, so firefighters can locate quicker. 2003 IFC-605.6 Open junction boxes and open wiring splices shall be prohibited. Location is above the back exit door. |