Case: T07FR01173

Parcel: 12206051C


Addresses:

4380 E GRANT RD


Inspection Status: Approved

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T07FR01173

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Approved

Date Description Inspector Results Comments
08/09/2007 VIOL - MEANS OF EGRESS Approved
06/20/2007 VIOL - MEANS OF EGRESS Violation Panic hardware hard to open:
1008.1.9 Panic and fire exit hardware. Where panic and fire exit hardware is installed, it shall comply with the following:
1. The actuating portion of the releasing device shall extend at least one-half of the door leaf width.
2. A maximum unlatching force of 15 pounds (67 N).

____ Service panic hardware to comply with acceptable opening resistance.
06/20/2007 VIOL - MEANS OF EGRESS Violation Exit access blocked:
1027.2 Reliability. Required exit accesses, exits or exit discharges shall be continuously maintained free from obstructions or impediments to full instant use in the case of fire or other
emergency. Security devices affecting means of egress shall be subject to approval of the fire code official.

1027.4 Furnishings and decorations. Furnishings, decorations or other objects shall not be placed so as to obstruct exits, access thereto, egress therefrom, or visibility thereof. Hangings and draperies shall not be placed over exit doors or otherwise be located to conceal or obstruct an exit. Mirrors shall not be placed on exit doors. Mirrors shall not be placed in or adjacent to any exit in such a manner as to confuse the direction of exit.

______ Clear exit path and keep it clear [36" minimum] Note: This pertains to the shield by the rear exit...see above code quote.
06/20/2007 VIOL - MEANS OF EGRESS Violation Exit signs:
TFC 1011.1 Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in an exit access corridor is more than 100 feet (30 480 mm) or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign.

______Place exit signs in an approved manner over the 3 exits.
06/20/2007 VIOL - MEANS OF EGRESS Violation "Night lighting" & Emergency lighting:
TFC 1006.1 Illumination required. The means of egress, including the exit discharge, shall be illuminated at all times the building space served by the means of egress is occupied.
and...
TFC 1006.3 Illumination emergency power. The power supply for means of egress illumination shall normally be provided by the premise's electrical supply. In the event of power supply failure, an emergency electrical system shall automatically illuminate the exit areas.

______ Install emergency lights at each exit. Also provide for "night lighting" on the main electricity.
06/20/2007 VIOL - MEANS OF EGRESS Violation Double keyed locks on doors:
1008.1.8 Door operations. Except as specifically permitted by this section egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort.

______ Remove Keyed dead bolts.