Case: T07FR01173

Parcel: 12206051C


Addresses:

4380 E GRANT RD


Inspection Status: Approved

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T07FR01173

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Approved

Date Description Inspector Results Comments
08/09/2007 VIOL - BUILDING SVCS & SYSTEMS Approved
06/20/2007 VIOL - BUILDING SVCS & SYSTEMS Violation Electrical wires extending through ceiling:

TFC 605.5 Flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors.

______ Please remove wires.
06/20/2007 VIOL - BUILDING SVCS & SYSTEMS Violation Extension cords:
TFC 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances.

_____Replace with approved power strips where needed.
06/20/2007 VIOL - BUILDING SVCS & SYSTEMS Violation Multiplug adapters:
TFC 605.4 Multiplug adapters. Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited.

______Remove noncomplying devices.
06/20/2007 VIOL - BUILDING SVCS & SYSTEMS Violation Open wire boxes/ splices:
TFC 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes.

______Cover wires in an approved manner [back room].