Case: T07FR01170

Parcel: 13419042D


Addresses:

7220 E BROADWAY BL

Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
07/03/2007 INSP - FULL Approved Final inspection.
06/19/2007 INSP - FULL Correction Required 2003 IFC-906.5 Fire extinguisher shall be located in conspicuous location where they will be readily accessable and immediately available for use.
2003 IFC-906.6 Fire extinguisher shall be installed so the top is not more than 5-feet from above the floor if less than 40 lbs. The extinguisher behind the counter floor was not serviced.
2003 IFC-315.2.1 Make sure storage is 18 inches below the sprinkler head.
2003 IFC-605.3 A working space and clearance of not less than 30 inches in width 36 inches in depth and 78 inches in height
2003 IFC-901 The fire sprinkler control and extra heads shall be accessable to the fire department at all times.