Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T07FR01170
Inspection Description - INSP - FULL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/03/2007 | INSP - FULL | Approved | Final inspection. | |
| 06/19/2007 | INSP - FULL | Correction Required | 2003 IFC-906.5 Fire extinguisher shall be located in conspicuous location where they will be readily accessable and immediately available for use. 2003 IFC-906.6 Fire extinguisher shall be installed so the top is not more than 5-feet from above the floor if less than 40 lbs. The extinguisher behind the counter floor was not serviced. 2003 IFC-315.2.1 Make sure storage is 18 inches below the sprinkler head. 2003 IFC-605.3 A working space and clearance of not less than 30 inches in width 36 inches in depth and 78 inches in height 2003 IFC-901 The fire sprinkler control and extra heads shall be accessable to the fire department at all times. |