Case: T07FR01124

Parcel: 126020020


Addresses:

4648 E SPEEDWAY BL


Inspection Status: Approved

Inspection History: VIOL - FIRE PROTECTION SYSTEMS

Case Number - T07FR01124

Inspection Description - VIOL - FIRE PROTECTION SYSTEMS

Inspection Status - Approved

Date Description Inspector Results Comments
07/31/2007 VIOL - FIRE PROTECTION SYSTEMS Approved
06/12/2007 VIOL - FIRE PROTECTION SYSTEMS Violation Extinguishers not mounted:
TFC 906.9 Height above floor. Portable fire extinguishers having a gross weight not exceeding 40 pounds (18 kg) shall be installed so that its top is not more than 5 feet (1524 mm) above the floor. Hand-held portable fire extinguishers having a gross weight exceeding 40 pounds (18 kg) shall be installed so that its top is not more than 3.5 feet (1067 mm) above the floor. The clearance between the floor and the bottom of installed hand-held extinguishers shall not be less than 4 inches (102 mm).

______Mount extinguishers in an approved manner.