Case: T07FR01104

Parcel: 12112365A


Addresses:

5146 E PIMA ST

Inspection Status: Approved

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Date Description Inspector Results Comments
08/01/2007 VIOL - BUILDING SVCS & SYSTEMS Approved
06/08/2007 VIOL - BUILDING SVCS & SYSTEMS Violation Extension cords:
TFC 605.5 Extension cords. Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances.

_____Replace with approved power strip.
06/08/2007 VIOL - BUILDING SVCS & SYSTEMS Violation Open wire boxes/ splices:
TFC 605.6 Unapproved conditions. Open junction boxes and open-wiring splices shall be prohibited. Approved covers shall be provided for all switch and electrical outlet boxes.

______Cover wires in an approved manner. [Wall plate- basement].
06/08/2007 VIOL - BUILDING SVCS & SYSTEMS Violation Open space in electrical panel:
TFC 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated.


_____Place an approved "blank" in the space.
06/08/2007 VIOL - BUILDING SVCS & SYSTEMS Violation Wires bad on compressor:
TFC 605.1 Abatement of electrical hazards. Identified electrical hazards shall be abated.

______ Replace wires in an approved manor. [and check all other equipment for electrical hazards]