Case: T07FR01102

Parcel: 13104399H


Addresses:

4777 E 29TH ST

Inspection Status: Approved

Inspection History: INSP - FULL

Date Description Inspector Results Comments
11/09/2007 INSP - FULL Approved Final inspection.
06/07/2007 INSP - FULL Correction Required 2003 IFC-105.6 The above ground tank (AST) is up to code. I need to check if we have permit papers on the 1000 gaollon tank.
2003 IFC-510 The fire department sprinkler system is in a small room the door shall be labeled RISER ROOM. This will help the firefighters locate quicker reduce water damage.
2003 IFC-3404.3.4.4 Flammable and commbustible liquids used for operation or maintenance equipment exceeding 10 gallons shall be stored in a flammable liquid storage cabinet.
The 704 sign shall be posted on thr door. By using the MSDS sheet you can optain the numbers to put on the 704.
Over all this was a safe building, fire safety.