Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T07FR01101
Inspection Description - INSP - FULL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/22/2007 | INSP - FULL | Approved | ||
06/07/2007 | INSP - FULL | Violation | On 6-7-07, a fire prevention inspection was conducted on the premises at 1413 North Columbus. The following Tucson Fire Code Violation(s) was noted: 1). Currently address does not meet Pima County Address Display Standards. This is violation of Tucson Fire Code section, 505.1 (modified) which states: Address numbers shall be in accordance with Pima County address display requirements. Address numbers to entrance to mobile Park shall be 12 inches in height. Enclosed is copy of these standards. 2). Currently in the area of Space #8, there is an excessive amount of combustible material. Items such as (but not limited to): household items, tires, furniture, clothes shall be removed. IFC 304.1.1 |