Case: T07FR01086

Parcel: 12212010A


Addresses:

4645 E SPEEDWAY BL


Inspection Status: Approved

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T07FR01086

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Approved

Date Description Inspector Results Comments
07/19/2007 VIOL - MEANS OF EGRESS Approved
06/12/2007 VIOL - MEANS OF EGRESS Correction Required TFC 1008.1 - Doors. Means of egress doors shall meet the requirements of this section. Doors serving a means of egress system shall meet the requirements of this section and Section 1017.2.
Doors provided for egress purposes in numbers greater than required by this code shall meet the requirements of this section.

TFC 1008.1.8.4 - Bolt locks. Manually operated flush bolts or surface bolts are not permitted.
Exceptions:
1. On doors not required for egress in individual dwelling units or sleeping units.
2. Where a pair of doors serves a storage or equipment room, manually operated edge- or surface-mounted bolts are permitted on the inactive leaf.

_____ Replace locking hardware on northeast door with approved locking device.
06/12/2007 VIOL - MEANS OF EGRESS Correction Required TFC 1027.2 - Reliability. Required exit accesses, exits or exit discharges shall be continuously maintained free from obstructions or impediments to full instant use in the case of fire or other emergency.

_____ Maintain a clear path to exit doors (forklift in front of door, produce area).
06/12/2007 VIOL - MEANS OF EGRESS Correction Required TFC 1023.6 - Access to a public way. The exit discharge shall provide a direct and unobstructed access to a public way.

TFC 1013.4.1 - In Group B and M occupancies, the minimum clear aisle width shall be determined by Section 1005.1 for the occupant load served, but shall not be less than 36 inches (914 mm).

_____ Maintain a 36" exit discharge from the northeast door off the loading dock.
06/12/2007 VIOL - MEANS OF EGRESS Correction Required TFC 1011.1 - Where required. Exits and exit access doors shall be marked by an approved exit sign readily visible from any direction of egress travel. Access to exits shall be marked by readily visible exit signs in cases where the exit or the path of egress travel is not immediately visible to the occupants. Exit sign placement shall be such that no point in an exit access corridor is more than 100 feet (30 480 mm) or the listed viewing distance for the sign, whichever is less, from the nearest visible exit sign.

_____ Remove cover from exit sign.