Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - MEANS OF EGRESS
Case Number - T07FR01085
Inspection Description - VIOL - MEANS OF EGRESS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
01/24/2008 | VIOL - MEANS OF EGRESS | Approved | All approved. | |
06/13/2007 | VIOL - MEANS OF EGRESS | Correction Required | TFC 1023.6 - Access to a public way. The exit discharge shall provide a direct and unobstructed access to a public way. _____ Egress discharge from kitchen area through gate north of building. |
|
06/13/2007 | VIOL - MEANS OF EGRESS | Correction Required | TFC 1027.2 - Reliability. Required exit accesses, exits or exit discharges shall be continuously maintained free from obstructions or impediments to full instant use in the case of fire or other emergency. Security devices affecting means of egress shall be subject to approval of the fire code official. _____ Move table near south east door. |
|
06/13/2007 | VIOL - MEANS OF EGRESS | Correction Required | TFC 1008.1.8 - Egress doors shall be readily openable from the egress side without the use of a key or special knowledge or effort. _____ Padlock on gate outside south dining area. _____ Padlock on gate outside bar. _____ Padlock on gate outside kitchen (above) |