Case: T07FR01085

Parcel: 12212001A


Addresses:

4699 E SPEEDWAY BL


Inspection Status: Approved

Inspection History: VIOL - INT.FINISH, DEC. MATL'S

Case Number - T07FR01085

Inspection Description - VIOL - INT.FINISH, DEC. MATL'S

Inspection Status - Approved

Date Description Inspector Results Comments
01/24/2008 VIOL - INT.FINISH, DEC. MATL'S Approved Treated with "Burn Barrier" - approved.
10/29/2007 VIOL - INT.FINISH, DEC. MATL'S Violation Flameproof decorations:
807.1 General requirements. In occupancies in Groups A, E, I and R-1 and dormitories in Group R-2, curtains, draperies, hangings and other decorative materials suspended from walls or ceilings shall meet the flame propagation performance criteria of NFPA 701 in accordance with Section 806.2 or be
noncombustible.

In Groups I-1 and I-2, combustible decorative materials shall meet the flame propagation criteria of NFPA 701 unless the decorative materials, including, but not limited to, photographs and paintings, are of such limited quantities that a hazard of fire development or spread is not present. In Group I-3, combustible
decorative materials are prohibited.
Fixed or movable walls and partitions, paneling, wall pads and crash pads, applied structurally or for decoration, acoustical correction, surface insulation or other purposes, shall be considered interior finish if they cover 10 percent or more of the wall or of the ceiling area, and shall not be considered decorative
materials or furnishings.
In Group B and M occupancies, fabric partitions suspended from the ceiling and not supported by the floor shall meet the flame propagation performance criteria in accordance with Section 807.2 and NFPA 701 or shall be noncombustible.

______ Treat the wall decorations and door opening blanket, (if needed), so they are noncombustable, and prove by documentation in either event.


Re-inspection date scheduled on or after Nov. 15, 2007.
If you have any questions or concerns please call Inspector Cobb at 791-4502
Thank you,

_____________________________________________
Brian Cobb, Inspector, Tucson Fire Department


__________________________I have received a copy of this inspection report.
Building Representative


_____________________________________________
Captain