Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: INSP - FULL
Case Number - T07FR01081
Inspection Description - INSP - FULL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/08/2007 | INSP - FULL | Approved | ||
06/05/2007 | INSP - FULL | Violation | 1). Ceiling tile shall be repaired in Suite 1100. IFC 703.1 2). Firestopping required in 11th floor computer room. IFC 703.1.1 3). Firestopping requited in 10th floor mech. Room. IFC 703.1. 4). Remove boxes from shelving in suite 903. IFC 903.3.3 5). Remove storage from shelves from within 2 feet from ceiling in suite 911. IFC 903.3.3 6). Firestopping required in 9th floor mech. Room piping. 7). Remove storage in 800 from within 2 feet from ceiling. IFC 903.3.3 8). Remove storage in suite 700 from within 2 feet from ceiling. IFC 903.3.3 9). Remove storage from within 2 feet from ceiling in suite 703. IFC 903.3.3 10). Fire extinguishers are out of service and shall be serviced or removed in suite 755. IFC 901.6 11). Firestopping requires in 6th floor mech. Room. IFC 703.1 12). Exit sign shall be repaired in 501. IFC 1026.3 13). Firestopping is required in 4th floor compute room. IFC 703.1 14). Cover electrical box in 4th floor mech. Room. IFC 605.1 15). Remove storage from within 2 feet from ceiling IFC 301. 16). Egress illumination light shall be repaired in basement storage. IFC 1026.5 17). Fire drill required. Drill shall be unannounced. IFC 404.1 Date shall be determined by 7-5-07. |