Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.
Inspection History Details
Inspection Status: Approved
Inspection History: VIOL - MEANS OF EGRESS
Case Number - T07FR01051
Inspection Description - VIOL - MEANS OF EGRESS
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/26/2007 | VIOL - MEANS OF EGRESS | Approved | All corrections have been made. | |
05/31/2007 | VIOL - MEANS OF EGRESS | Violation | IFC 1011.2 Exit signs shall be externally or internally lit. Cause your exit sign in the diner and kitchen area to light. | |
05/31/2007 | VIOL - MEANS OF EGRESS | Violation | IFC 1011.1 Exits shall be marked with an approved sign visible from any direction of egress travel. Your kitchen exit sign shall be moved over the exit where it is visible from all directions of travel. | |
05/31/2007 | VIOL - MEANS OF EGRESS | Violation | IFC 1027.4 Furnishings, decorations or other objects shall not be placed so as to obstruct exits, access thereto, egress therefrom, or visibility thereof. Remove all furniture and storage blocking your exit from the office. | |
05/31/2007 | VIOL - MEANS OF EGRESS | Violation | IFC 1006.1 The means of egress, including the exit discharge, shall be illuminated at all times the building space served byt he means of egress is occupied. Cause your emergency lighting to operate properly. |