Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case: T07FR01051

Parcel: 13017149A


Addresses:

1835 S ALVERNON WY


Inspection Status: Approved

Inspection History: VIOL - MEANS OF EGRESS

Case Number - T07FR01051

Inspection Description - VIOL - MEANS OF EGRESS

Inspection Status - Approved

Date Description Inspector Results Comments
06/26/2007 VIOL - MEANS OF EGRESS Approved All corrections have been made.
05/31/2007 VIOL - MEANS OF EGRESS Violation IFC 1011.2 Exit signs shall be externally or internally lit. Cause your exit sign in the diner and kitchen area to light.
05/31/2007 VIOL - MEANS OF EGRESS Violation IFC 1011.1 Exits shall be marked with an approved sign visible from any direction of egress travel. Your kitchen exit sign shall be moved over the exit where it is visible from all directions of travel.
05/31/2007 VIOL - MEANS OF EGRESS Violation IFC 1027.4 Furnishings, decorations or other objects shall not be placed so as to obstruct exits, access thereto, egress therefrom, or visibility thereof. Remove all furniture and storage blocking your exit from the office.
05/31/2007 VIOL - MEANS OF EGRESS Violation IFC 1006.1 The means of egress, including the exit discharge, shall be illuminated at all times the building space served byt he means of egress is occupied. Cause your emergency lighting to operate properly.