Inspection Status: Approved
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
| Date |
Description |
Inspector |
Results |
Comments |
| 06/29/2007 |
VIOL - BUILDING SVCS & SYSTEMS |
|
Approved |
Last correction made today. Wiring in kitchen closet placed in Jbox. |
| 05/31/2007 |
VIOL - BUILDING SVCS & SYSTEMS |
|
Violation |
IFC 605.6 Open wiring splices are not permitted. Place all open wiring in an approved junction box or physically remove from the premisis. ( Outdoor W wall, kitchen closet, near meat freezer, balast in dry goods room, AC thermostat). |
| 05/31/2007 |
VIOL - BUILDING SVCS & SYSTEMS |
|
Violation |
IFC 605.6 Approved covers shall be provided for all switches and electrical outlet boxes. Place a face plate on the outlet near the cutting block bench, on the wall near the grill, and near the bar. |
| 05/31/2007 |
VIOL - BUILDING SVCS & SYSTEMS |
|
Violation |
IFC 605.3 No storage of materials shall block the working space in front of the electrical panels. Move items stored in front of electric panel next to jello freezer. |