Case: T07FR01048

Parcel: 13421083B


Addresses:

6940 E BROADWAY BL


Inspection Status: Approved

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T07FR01048

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Approved

Date Description Inspector Results Comments
06/29/2007 VIOL - BUILDING SVCS & SYSTEMS Approved Last correction made today. Wiring in kitchen closet placed in Jbox.
05/31/2007 VIOL - BUILDING SVCS & SYSTEMS Violation IFC 605.6 Open wiring splices are not permitted. Place all open wiring in an approved junction box or physically remove from the premisis. ( Outdoor W wall, kitchen closet, near meat freezer, balast in dry goods room, AC thermostat).
05/31/2007 VIOL - BUILDING SVCS & SYSTEMS Violation IFC 605.6 Approved covers shall be provided for all switches and electrical outlet boxes. Place a face plate on the outlet near the cutting block bench, on the wall near the grill, and near the bar.
05/31/2007 VIOL - BUILDING SVCS & SYSTEMS Violation IFC 605.3 No storage of materials shall block the working space in front of the electrical panels. Move items stored in front of electric panel next to jello freezer.