Case: T07FR01026

Parcel: 11941176H


Addresses:

1785 W AJO WY


Inspection Status: Approved

Inspection History: INSP - FULL

Case Number - T07FR01026

Inspection Description - INSP - FULL

Inspection Status - Approved

Date Description Inspector Results Comments
11/09/2007 INSP - FULL Approved Final inspection.
06/15/2007 INSP - FULL Partial Approval The C of O referred to D. S. D.
Lisa Frank will be the representative for this addrees.
(573) 449-2643. The sprinkler system needs to be secured , gate will not lock.
05/29/2007 INSP - FULL Correction Required 2003 IFC- 605.5.2 A working space and clearance of not less than 30 inches in width 36 inches in depth and 78 inches in height shall be provided in front of electrical service equipment(panel).
2003 IFC-906 The fire sprinkler system is outside in a fenced area. The gate is not secured, need to fix the handle.
2003 IFC-105.3.3 Certificate of Occupancy shall be posted in the business.