Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you can not find what you are looking for please submit a records request.

Case: T07FR01017

Parcel: 133231420


Addresses:

7707 E BROADWAY BL


Inspection Status: Continued

Inspection History: VIOL - BUILDING SVCS & SYSTEMS

Case Number - T07FR01017

Inspection Description - VIOL - BUILDING SVCS & SYSTEMS

Inspection Status - Continued

Date Description Inspector Results Comments
06/14/2007 VIOL - BUILDING SVCS & SYSTEMS Continued This is an ongoing problem. Manager assured that they would remove all ungrounded/unprotected extension cords but be sure that they do not start using them again!
05/29/2007 VIOL - BUILDING SVCS & SYSTEMS Correction Required TFC 605.4 - Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited.

_____ Remove noncomplying devices.

TFC 605.4.1 - Relocatable power taps shall be of the polarized or grounded type, equipped with overcurrent protection, and shall be listed.

_____ Replace with approved power strip.

TFC 605.5 - Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances.

_____ Remove all flexable cords from under rugs

_____ Protect all flexable elecrtical wiring serving relocatable power taps from damage, or replace with approved permanent electrical power source.