Inspection History Details
Inspection Status: Continued
Inspection History: VIOL - BUILDING SVCS & SYSTEMS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/14/2007 | VIOL - BUILDING SVCS & SYSTEMS | Continued | This is an ongoing problem. Manager assured that they would remove all ungrounded/unprotected extension cords but be sure that they do not start using them again! | |
| 05/29/2007 | VIOL - BUILDING SVCS & SYSTEMS | Correction Required | TFC 605.4 - Multiplug adapters, such as cube adapters, unfused plug strips or any other device not complying with the ICC Electrical Code shall be prohibited. _____ Remove noncomplying devices. TFC 605.4.1 - Relocatable power taps shall be of the polarized or grounded type, equipped with overcurrent protection, and shall be listed. _____ Replace with approved power strip. TFC 605.5 - Extension cords and flexible cords shall not be a substitute for permanent wiring. Extension cords and flexible cords shall not be affixed to structures, extended through walls, ceilings or floors, or under doors or floor coverings, nor shall such cords be subject to environmental damage or physical impact. Extension cords shall be used only with portable appliances. _____ Remove all flexable cords from under rugs _____ Protect all flexable elecrtical wiring serving relocatable power taps from damage, or replace with approved permanent electrical power source. |