Case: T07FR00990

Parcel: 10510010D


Addresses:

333 E WETMORE RD


Inspection Status: Violation

Inspection History: INSP - FULL

Case Number - T07FR00990

Inspection Description - INSP - FULL

Inspection Status - Violation

Date Description Inspector Results Comments
05/22/2007 INSP - FULL Violation 1). Fire sprinkler test and inspection report shall be submitted and all repairs shall be completed. IFC 901.6
2). Fire alarm test report shall be submitted and all required repairs shall be completed. IFC 901.6
3). Fire drill shall be conducted. Date to be determined by 6-15-07. IFC 404.2
4). Elevator room. Remove all combustible materials 30 inches from electrical service. IFC 605.3
5). Elevator room. Remount fire extinguisher. IFC 901.6
6). Repair fire stopping on 6th floor. IFC 703.1.1
7). Repair egress illumination on 6th and 5th floors. IFC 1027
8). Storage shall be orderly. 4th floor IT room. 304.2
9). Currently cabinet or monitors are interfering with access to pre action system. Move cabinet or excess monitors. IFC 901.6