Inspection Status: Correction Required
Inspection History: INSP - FULL
Case Number - T07FR00977
Inspection Description - INSP - FULL
Inspection Status - Correction Required
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/18/2007 | INSP - FULL | Correction Required | 2003 IFC-1008.1.8.3 The front main exit door has a key lock, there for a sign shall be posted: THIS DOOR TO REMAIN UNLOCKED WHEN BUIDLING IS OCCUPIED. 2003 IFC-1003.6 Obstruction to exit shall no be placed in the required width and exit shall not be obstructed in any manner. 2003 IFC-3003.3.3 Compress gas cylinders shall be secured to prevent falling. Secure to a fix object with restraints. 2003 IFC-508.54. The fire department connections and valves shall not be obstructed or blocked in any manner. |